    室内消火栓的检查内容都有哪些?
    2021-04-13 15:51:43
    室内消火栓是常用的消防器材,但是随着时间的增长消火栓难免会出现问题,这就需要我们经常进行检查维护了,那你知道消火栓的检查内容都有哪些吗?下面,J9九游会登录厂家带大家一起了解一下,希望能帮助到你!
    Indoor fire hydrant is a common fire equipment, but with the growth of time, fire hydrant will inevitably have problems, which requires us to check and maintain frequently. Do you know what the inspection contents of fire hydrant are? Next, fire hydrant guardrail manufacturers take you to understand, hope to help you!
    1、外观质量和标志。消火栓箱箱体应设耐久性铭牌,包括以下内容:产品名称,产品型号,批准文件的编号,注册商标或厂名,生产日期,执行标准。
    1. Appearance and quality marks. The fire hydrant box shall be provided with durability nameplate, including the following contents: product name, product model, number of approval document, registered trademark or factory name, production date and executive standard.
    消火栓应在阀体或阀盖上铸出型号、规格和商标。现场检查时可以用小刀轻刮箱体内外表面图层,查看是否经过防腐处理。此外目测栓箱箱门正面应以直观、醒目、匀整的字体标注“消火栓”字样,且字体不得小于:高100mm,宽80mm。

    The model, specification and trademark of fire hydrant shall be cast on the valve body or cover. During on-site inspection, you can use a knife to gently scrape the inner and outer surface layer of the box to check whether it has been treated with anti-corrosion treatment. In addition, the word "fire hydrant" shall be marked on the front of the door of the visual inspection hydrant box in a visual, eye-catching and neat font, and the font shall not be less than: 100 mm high and 80 mm wide.

    J9九游会登录

    2、器材的配置和性能室内消火栓箱按照该产品的检验报告,箱内消防器材的配置应该与报告一致,且栓箱内配置的消防器材(水枪、水带等)符合各产品现场检查的要求。
    2. According to the inspection report of the product, the configuration of fire-fighting equipment in the indoor hydrant box should be consistent with the report, and the fire-fighting equipment (water gun, water hose, etc.) in the hydrant box should meet the requirements of on-site inspection of each product.
    3、箱门消火栓箱应设置门锁或箱门关紧装置。设置门锁的栓箱,除箱门安装玻璃者以及能被击碎的透明材料外,均应设置箱门紧急开启的手动机构,应保证在没有钥匙的情况下开启灵活。且箱门开启角度不得小于120°,并无卡阻现象。
    3. The fire hydrant box of box door shall be equipped with door lock or door locking device. For the bolt box with door lock, the manual mechanism for emergency opening of the door shall be set, except for the glass installation of the door and the transparent material that can be broken, so as to ensure that the door can be opened flexibly without a key. And the opening angle of the box door shall not be less than 120 ° without jamming.
    4、水带安置。盘卷式栓箱的水带盘从挂臂上取出应无卡阻。
    4. Hose placement. The hose tray of the coil type bolt box shall be taken out from the hanging arm without jamming.
    5、材料消火栓箱刮开箱体涂层,使用千分尺进行测量,箱体应使用厚度不小于1.2mm的薄钢板或铝合金材料制造,箱门玻璃厚度不小于4.0mm。
    5. The coating of material fire hydrant box shall be scraped off and measured with micrometer. The box shall be made of steel sheet or aluminum alloy with thickness not less than 1.2mm, and the thickness of door glass shall not be less than 4.0mm.
    以上五点就是室内消火栓的检查内容,相信大家在阅读完本文的内容之后能够对消火栓有一定的认识和了解,希望以上内容能帮助到你。另外,若你想要了解更多相关资讯,欢迎点击咨询J9九游会登录厂家
    The above five points are the inspection contents of indoor fire hydrant. I believe you can have a certain understanding of fire hydrant after reading this article. I hope the above contents can help you. In addition, if you want to know more information, please click to consult fire hydrant guardrail manufacturer 。